| Питание | |
|---|---|
| Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Minimum switch current | 2 mA / 24 V DC |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
| Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Power consumption | max. 1.5 W |
| Rated voltage | U r | 20 ... 30 V DC |
| Характеристики по постоянному и переменному току | |
| Accuracy | 5 % (S3 = I), 30 % (S3 = II) |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
| Frequency range | ≤ 2 kHz |
| Условия эксплуатации и корпус | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Height 119 mm Width 20 mm Depth 115 mm | Height | 119 mm | Width | 20 mm | Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Другое | |
| Configuration | via DIP switches |
| Connection | terminals 14+, 15- |
| Connection side | field side |
| Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
| Control elements | DIP switch |
| Control input | sensor power supply approx. 8.2 V, impedance 1.2 kΩ |
| Degree of protection | IEC 60529:2001 |
| Depth | 115 mm |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/35/EU | EN 61010-1:2010 |
| Directive 2014/35/EU EN 61010-1:2010 | Directive 2014/35/EU | EN 61010-1:2010 |
| Display elements | LEDs |
| Electromagnetic compatibility | NE 21:2006 |
| Input | EN 60947-5-6:2000 |
| Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Labeling | space for labeling at the front |
| Line fault detection | not available |
| Mass | approx. 150 g |
| Mechanical life | 10 7 switching cycles |
| Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Programming | via DIP switch and programmable |
| Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion |
| Rated values | acc. to EN 60947-5-6 (NAMUR) |
| Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs |
| Safety Integrity Level (SIL) | SIL 2 |
| Signal type | Digital Input |
| Start-up override | 5 seconds or 20 seconds, programmable |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Trip value | f max | for standstill monitoring: 0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz adjustable via DIP switch (S1 and S2) |
| Width | 20 mm |