All alternatives

View full report

Technical parameters

Power
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Minimum switch current2 mA / 24 V DC
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Power consumptionmax. 1.5 W
Rated voltageU r | 20 ... 30 V DC
AC and DC characteristics
Accuracy5 % (S3 = I), 30 % (S3 = II)
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Frequency range≤ 2 kHz
Environment and package
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Height 119 mm Width 20 mm Depth 115 mmHeight | 119 mm | Width | 20 mm | Depth | 115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Other
Configurationvia DIP switches
Connectionterminals 14+, 15-
Connection sidefield side
Contact loading253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load
Control elementsDIP switch
Control inputsensor power supply approx. 8.2 V, impedance 1.2 kΩ
Degree of protectionIEC 60529:2001
Depth115 mm
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/35/EUEN 61010-1:2010
Directive 2014/35/EU EN 61010-1:2010Directive 2014/35/EU | EN 61010-1:2010
Display elementsLEDs
Electromagnetic compatibilityNE 21:2006
InputEN 60947-5-6:2000
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Labelingspace for labeling at the front
Line fault detectionnot available
Massapprox. 150 g
Mechanical life10 7 switching cycles
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Programmingvia DIP switch and programmable
Pulse duration> 200 µs for standstill monitoring, > 250 µs for rotation direction detecion
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Rotation direction detection90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs
Safety Integrity Level (SIL)SIL 2
Signal typeDigital Input
Start-up override5 seconds or 20 seconds, programmable
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Trip valuef max | for standstill monitoring: 0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz adjustable via DIP switch (S1 and S2)
Width20 mm

Documents

No documents are linked to this part yet.