Ethernet IO-Link module with 8 inputs/outputs

Спросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Current consumptiontyp. 200 mA
Current loading capacityMax. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 9 A per module
Nominal voltage24 V DC
Output currentI e | max. 500 mA per port (X1 - X8) Via C/Q (pin 4) In addition, a maximum of 2 A per port (X5 – X8) Via U Aux (pin 2)
Rated operating voltageU e | 18 ... 30 V
Sensor supplymax. 500 mA per port (X1 - X8) via L+ (pin 1)
Характеристики по постоянному и переменному току
Noise immunityEN 61000-6-2:2005
Условия эксплуатации и корпус
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Cold start temperature-40 °C (-40 °F)
Height200 mm
Height 200 mm Width 59.6 mm Length 21 mmHeight | 200 mm | Width | 59.6 mm | Length | 21 mm
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Другое
Altitude0 ... 2000 m
ConnectionPower Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded
Construction typeField housing
Contact elementsPA
ContactsCuSn, gold-plated CuNi, gold-plated
Contacts CuSn, gold-plated CuNi, gold-plated Housing Diecast zinc Seal FKMContacts | CuSn, gold-plated CuNi, gold-plated | Housing | Diecast zinc | Seal | FKM
Degree of protectionEN 60529:2000
Directive 2014/30/EUEN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Directive 2014/30/EU EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011Directive 2014/30/EU | EN 61000-6-2:2005, EN 61000-6-4:2007+A1:2011
Emitted interferenceEN 61000-6-4:2007+A1:2011
Fieldbus standardType 1 according to IEC 61131-2
Galvanic isolationbetween U S and U L
HousingDiecast zinc
Interface typeIndustrial Ethernet
LED indicationsee manual
Length21 mm
Mass500 g
MTTF574 a
Number/Type4 x IO-Link Class A (X1 – X4) 4 x IO-Link Class B (X5 – X8) Configurable as: max. 8 IO-Link and 4 digital inputs and outputs max. 12 digital inputs and 4 digital outputs max. 12 digital outputs and 4 digital inputs short-circuit protected
PhysicalM12, D-coded
Pollution degree3
ProtocolPROFINET IO with media redundancy protocol (MRP) EtherNet/IP with Device Level Ring (DLR)
Relative humiditymax. 95 %
Rotary switchSetting the fieldbus protocol
SealFKM
Shock and impact resistance50 g, 11 ms, all axes
Shock resistanceEN 61131-2:2004
Tightening torque, cable gland0.6 Nm
Tightening torque, fastening screws1 Nm
Tightening torque of clamping screws0.5 Nm
Transfer rate10/100 Mbps
UL File NumberE223772
Vibration resistance15 g at 5 - 500 Hz
Width59.6 mm

Изображения