Pepperl+Fuchs, Inc.Германия

42517

Производится

LCD batch controller with 1 relay output and 230 V<sub>AC</sub> supply voltage

Спросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Low Voltage Directive 2006/95/ECEN 61010-1:2001; protection class: 2
Low Voltage Directive 2006/95/EC EN 61010-1:2001; protection class: 2 EMC Directive 2004/108/EC EN 61000-6-2:2005, EN 50295:1999Low Voltage Directive 2006/95/EC | EN 61010-1:2001; protection class: 2 | EMC Directive 2004/108/EC | EN 61000-6-2:2005, EN 50295:1999
Operating voltageU B | 230 V AC
Power consumptionP 0 | max. 6.5 VA
Sensor supply14.4 ... 27.6 V DC max. 50 mA at 230 V AC
Switching currentmax. 3 A AC/DC, min. 30 mA DC,
Switching powermax. 750 VA / 90 W
Switching voltagemax. 250 V AC / 110 V DC
Характеристики по постоянному и переменному току
Counting frequency30 Hz / 5 kHz
Impedance10 kOhm
Условия эксплуатации и корпус
Ambient temperature-10 ... 50 °C (14 ... 122 °F)
Dimensions48 mm x 48 mm x 109.8 mm
Storage temperature-25 ... 75 °C (-13 ... 167 °F)
Другое
Altitude0 ... 2000 m
ConnectionCounter inputs: A and B Control/reset inputs: LOCK, RESET
Data storage> 10 years, EEPROM
Decimal point0 to max 5 fractional digits
Degree of protectionIP65 (front)
Display valuedigit height 9 mm
Electrical life5 x 10 4 cycles at 3 A
EMC Directive 2004/108/ECEN 61000-6-2:2005, EN 50295:1999
Emitted interferenceDIN EN 55011:2009, Class B
FusingT 0.1 A
High3.5 ... 30 V DC
High 3.5 ... 30 V DC Low 0 ... 2 V DCHigh | 3.5 ... 30 V DC | Low | 0 ... 2 V DC
Key interlockvia "high" potential at "LOCK" input
Low0 ... 2 V DC
Massapprox. 230 g
Mechanical life2 x 10 7 switching cycles
Mech. capacityEN 60068-2-6:2008 10 … 55 Hz / 1 mm / XYZ 30 min in each direction
Minimum pulse durationControl/reset inputs: static / 1 ms
Pollution degree2
Pre-selectionsingle
Programmingkeypad-driven menu
Pulse counterCounting with counting direction (cnt.dir), difference counting (up.dn), up/down counting (quad),
Relative humidity≤ 93 % at 40 °C (non-condensing)
Relaychangeover contact
Resetmanually or external
Response time< 15 ms pulse counter < 10 ms time counter
Scale factor0.0001 ... 99.9999
Shock and impact resistanceEN 60068-2-27:1995 100 G / 2 ms / XYZ 3 times in each direction
TimerTime measurement via GATE input (FrErun), counter input A: Start, counter input B: Stop (InpA.InpB.), counter input B: Start/Stop (InpB.InpB.),
Type2-line, 2 x 6-digit LC display with leading sign

Изображения

Документы