Поиск аналогов электронных компонентов
4115
Pepperl+Fuchs, Inc.Германия

4115

Производится

G4 module IP65, 4 inputs (PNP) and 3 electronic outputs

Подобрать аналогСпросить AI FAE

Все аналоги

Полный отчёт

Технические параметры

Питание
Auxiliary voltage (output)U AUX | 24 V DC ± 15 % PELV
Current4 A total OUT 1, OUT 2: 2 A per output OUT 3: 1.5 A
Current loading capacity≤ 180 mA (T B ≤ 40 °C), ≤ 140 mA (T B ≤ 60 °C), short-circuit protected
Input current≤ 9 mA (limited internally)
Rated operating currentI e | ≤ 40 mA (without sensors) / max. 240 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface
Voltage21 ... 31 V
Характеристики по постоянному и переменному току
Noise immunityEN 61000-6-2:2005
Условия эксплуатации и корпус
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Height71 mm
Height 71 mm Width 90 mm Length 102 mmHeight | 71 mm | Width | 90 mm | Length | 102 mm
MountingDIN rail or screw mounting
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Другое
0 (unattenuated)≤ 3 mA
0 (unattenuated) ≤ 3 mA 1 (attenuated) ≥ 5 mA0 (unattenuated) | ≤ 3 mA | 1 (attenuated) | ≥ 5 mA
1 (attenuated)≥ 5 mA
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Climatic conditionsFor indoor use only
Connectioncable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals
D0IN1 OUT1
D0 IN1 OUT1 D1 IN2 OUT2 D2 IN3 OUT3 D3 IN4 -D0 | IN1 OUT1 | D1 | IN2 OUT2 | D2 | IN3 OUT3 | D3 | IN4 -
D1IN2 OUT2
D2IN3 OUT3
D3IN4 -
Data bits (function via AS-Interface)Input Output
Degree of protectionEN 60529:2000
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPA 6 GF30
Housing PA 6 GF30Housing | PA 6 GF30
ID1 code7
ID2 code0
ID codeA
InputEN 61131-2:2007
IO code7
LED AUXext. auxiliary voltage U AUX ; LED green
LED INswitching state (input); 4 LED yellow
LED OUTSwitching state (output); 3 LED yellow
LED PWR/FAULTdual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs
Length102 mm
Mass350 g
Node typeA/B node
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC
P0not used
P0 not used P1 not used P2 not used P3 not usedP0 | not used | P1 | not used | P2 | not used | P3 | not used
P1not used
P2not used
P3not used
Parameter bits (programmable via AS-i)function
Pollution degree3
ProfileS-7.A.0
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Surge protectionU AUX , U in : Over voltage category III, safe isolated power supplies (PELV)
Switching pointaccording to DIN EN 61131-2 (Type 2)
Tightening torque, housing screws0.8 Nm
UL File NumberE223772
Width90 mm

Изображения

Документы

К этому компоненту пока не привязаны документы.