All alternatives

View full report

Technical parameters

Power
Inrush current16 A
Inrush current duration10 s
Reference voltage24 V
Reference voltage 2120 VAC
Reference voltage 2 ohmic120 VAC
Reference voltage dc ohmic30 VDC
Reference voltage inductive maximum250 VAC
Reference voltage ohmic250 VAC
Switching current20 mA
Switching current 2 inductive2 A
Switching current 2 ohmic10 A
Switching current dc ohmic1 A
Switching current inductive1,6 A
Switching current ohmic5 A
Environment and package
Height47 mm
MountingClip for 35 mm DIN rail, EN 60715
Operating temperature-40 °C - 80 °C
Storage temperature-45 °C - 80 °C
Switch-off temperature15 °C
Switch-off temperature 2 tolerance± 6 K
Switch-off temperature tolerance± 5 K
Switch-on temperature5 °C
Switch-on temperature 2 tolerance± 7 K
Switch-on temperature tolerance± 5 K
Other
01163.0-00+40 °C | 50 °C
01163.0-02+25 °C | 35 °C
AC/DCAC;DC
CasingPlastic to UL94 V-0, light grey
Connection2-pole clamp: Rigid wire/stranded wire 2.5 mm² (AWG 14)
Contact typeSnap-action contact
Depth33 mm
DesignNormally closed (NC); Normally open (NO)
Device typeThermostats
Minimal switching capacity0,48 W
NoteOther switch-on/switch-off temperatures on request. Wire end ferrules must be used for connections with stranded wires. Switching of resistive load (switching of inductive load).
Operating humidity≤90 % RH
Protection typeIP20
SensorThermostatic bimetal
Service life>100000 cycles
Setting rangefirm
Storage humidity≤90 % RH
Switching capacityAC 250 V: 5 (1.6) A; AC 120 V: 10 (2) A; DC 24-72 V: 30 W
Torque0,8 Nm max.
Weight40 g
Width63 mm

Documents