All alternatives

View full report

Technical parameters

Power
1) Voltage Rating600 V RMS
Environment and package
1) Temperature Range-40 to 90°C(static), -5 to 90°C (dynamic)
Other
1) Component 14 X 1 COND
(1) PrintALPHANUMERIC NUMBERS - 1-ONE ALTERNATING AND INVERTED
1) ULa) Component 1
2) Bend Radius6X Cable Diameter(static), 8X Cable Diameter(dynamic)
2) Cable Assembly4 Components Cabled
2) Capacitance33 pF/ft @1 kHz, Nominal Conductor to Conductor
(2) Color CodeAlpha Wire Color Code RX
3) California Proposition 65This product may contain substances known to the State of California to cause Cancer or Reproductive Harm, but is exempt from labeling based on the Consent Judgement. See the Alpha Wire website for more information.
3) Inductance0.16 μH/ft, Nominal
3) OtherConductors ASTM Class K
3) Pull Tension330 Lbs, Maximum
4) CEEU Low Voltage Directive 2014/35/EU
4) Conductor DCR1.03 Ω/1000ft @20°C, Nominal
4) Sunlight ResistanceYes
a) Color(s)BLACK
a) Twists3.0 Twists/foot (min)
b) OrientationComponents to be arranged from OUTSIDE LAYER to INSIDE LAYER
b) Overall-40C
b) PrintALPHA WIRE-* P/N F10004RW 4C 10 AWG (5.32mm2) THWN-2 SERIES F (UL) TYPE TC-ER 90C WET/DRY 600V OIL RES I/II -40C SUN RES OR C(UL) CIC CONTROL/TC 10 AWG -40C 90C WET 90C DRY PVC/NYLON INS FT4 OR CRU AWM I/II A/B 90C 600V FT4 CE ROHS (DATE CODE) (SEQ FOOTAGE) * = Factory Code [Note: Product may have c(UL) or CSA markings depending upon plant of manufacture.]
c) Core WrapREMAY Tape, 25% Overlap, Min.
ColorGREEN/YELLOW
Cond1
C(UL) CIC CONTROL90°C / 600V V RMS
C(UL) TC90°C Dry / 90°C Wet / 600V V RMS
Electrical Properties(For Engineering purposes only)
PackagingFlange x Traverse x Barrel (inches)
TC90°C Dry / 90°C Wet / 600 V RMS
THWN-290°C Dry / 90°C Wet / 600 V RMS

Documents