| Power | |
|---|---|
| Rated Voltage | 400VAC/50Hz~1140VAC/50Hz |
| Test Voltage between Terminals | 2.15Ur(AC)10S 20℃ |
| Environment and package | |
| Operating Temperature Range | -40℃~+55℃ (Max.+85℃) |
| Test Voltage btw Terminals & Case | 1000+2×Ur(VAC) 50Hz 60S (min 3000VAC) |
| Other | |
| Capacity Range | 3×40μF~3×500μF |
| Capacity Tolerance | ±5%(J); ±10%(K) |
| Dissipation Factor | tgδ≤2×10-3 , at 20℃,100Hz |
| Insulation Resistance | C•R≥10000S,at 100VDC,20℃,60S |
| Life Expectancy | 100000hrs ( Ur hotspot ≤ 55℃) |
| Maximum altitude | 2000m |
| Reference Standards | GB/T 17702 IEC 61071 |