All alternatives

View full report

Technical parameters

Power
Current4 ... 20 mA
Input/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Input voltageopen loop voltage of the control system < 30 V, in line fault mode < 60 V
Maximum safe voltageU m | 250 V AC (Attention! U m is no rated voltage.)
Maximum safe voltage U m 250 V AC (Attention! U m is no rated voltage.)Maximum safe voltage | U m | 250 V AC (Attention! U m is no rated voltage.)
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
PowerP o | 630 mW
Power consumption≤ 800 mW
Power dissipation≤ 700 mW at 20 mA and 500 Ω load
Rated currentI r | ≤ 33 mA at 24 V
Rated voltageU r | 19 ... 30 V DC
Voltage≥ 13 V at 20 mA
Voltage dropapprox. 6 V at 20 mA
Voltage U o 25.2 V Current I o 100 mA Power P o 630 mW Internal capacitance C i 5.7 nF Internal inductance L i negligibleVoltage | U o | 25.2 V | Current | I o | 100 mA | Power | P o | 630 mW | Internal capacitance | C i | 5.7 nF | Internal inductance | L i | negligible
AC and DC characteristics
Frequency rangefield side into the control side: bandwidth with 0.5 V pp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mA pp signal 0 ... 3 kHz (-3 dB)
Protection against electrical shockUL 61010-1:2012
Ripple≤ 10 %
Rise time10 to 90 % ≤ 10 ms
Environment and package
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Dimensions12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))Influence of ambient temperature | < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F))
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Other
CertificateCESI 20 ATEX 017 X
ConnectionPower Rail or terminals 9+, 10-
Connection sidecontrol side
Control drawing116-0471 (cULus)
Control drawing 116-0471 (cULus)Control drawing | 116-0471 (cULus)
Degree of protectionIEC 60529
Deviationat 20 °C (68 °F), 4 ... 20 mA < 0.1 % of full scale, incl. non-linearity and hysteresis
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015
Directive 2014/34/EU EN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-7:2015
Display elementsLEDs
Electromagnetic compatibilityNE 21:2017 EN 61326-3-2:2018
Equipmentterminals 1+, 2-
EU-type examination certificateCESI 20 ATEX 016 X
IECEx certificateIECEx CES 20.0009X
IECEx certificate IECEx CES 20.0009X IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 GcIECEx certificate | IECEx CES 20.0009X | IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
Input/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Input resistance> 100 kΩ, with field wiring open or < 50 Ω
Input signal4 ... 20 mA , limited to approx. 25 mA
Internal capacitanceC i | 5.7 nF
Internal inductanceL i | negligible
Labelingspace for labeling at the front
Line fault detectionfield wiring open or < 50 Ω and test current < 2 mA
Load100 ... 650 Ω
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I Output Ex iaMarking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I | Output | Ex ia
Marking II 3G Ex ec IIC T4 GcMarking | II 3G Ex ec IIC T4 Gc
Massapprox. 100 g
OutputEx ia
Safety Integrity Level (SIL)SIL 3
Signal typeAnalog output
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
UL approvalE106378

Documents

No documents are linked to this part yet.