All alternatives

View full report

Technical parameters

Power
No-load supply currentI 0 | ≤ 10 mA
Off-state currentI r | 0 ... 0.2 mA
Operating currentI L | 0 ... 100 mA
Operating voltageU B | 5 ... 30 V
Voltage dropU d | ≤ 1.5 V
AC and DC characteristics
Switching frequencyf | 0 ... 4500 Hz
Time delay before availabilityt v | ≤ 100 ms
Environment and package
Ambient temperature-40 ... 85 °C (-40 ... 185 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Other
Actuating elementmild steel, e. g. 1.0037, SR235JR (formerly St37-2) 8 mm x 8 mm x 1 mm
Assured operating distances a | 0 ... 2.43 mm
Bending radius> 10 x cable diameter
Cable diameter3.3 mm ± 0.15 mm
CCC approvalCCC approval / marking not required for products rated ≤36 V
Colorblack
Connection typecable
Core cross section0.14 mm 2
Degree of protectionIP65 / IP66 / IP67
Diagnostic Coverage (DC)0 %
Diameter8 mm
Housing materialStainless steel 1.4305 / AISI 303
HysteresisH | typ. 5%
Installationnon-flush
LengthL | 2 m
Length 40 mm Diameter 8 mmLength | 40 mm | Diameter | 8 mm
MaterialPUR
Mission Time (T M )20 a
MTTF d960 a
Number of cores3
Output polarityDC
Output typePNP
Rated operating distances n | 3 mm
Reduction factor r 3040.75
Reduction factor r Al0.5
Reduction factor r Brass0.5
Reduction factor r Cu0.4
Reverse polarity protectionreverse polarity protected
Scope of delivery2 hex nuts included
Sensing faceLCP
Short-circuit protectionpulsing
StandardsEN IEC 60947-5-2
Standards EN IEC 60947-5-2Standards | EN IEC 60947-5-2
Switching functionNormally closed (NC)
Switching state indicatorLED, yellow
UL approvalcULus Listed Load Type: General Purpose Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 30 V DC Output Switching Current: 100 mA
Wire end ferrulesyes

Documents

No documents are linked to this part yet.