All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Current | I o | 0.5 mA |
| Current output | 4 ... 20 mA , limited to ≤ 35 mA |
| Current range | 0 ... 20 mA , load ≤ 50 Ω |
| Influence of supply voltage | 6.5 ppm/V |
| Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
| Marking II (1)GD [EEx ia] IIC Input EEx ia IIC Voltage U o 9.6 V Current I o 0.5 mA Power P o 1.1 mW linear characteristic | Marking | II (1)GD [EEx ia] IIC | Input | EEx ia IIC | Voltage | U o | 9.6 V | Current | I o | 0.5 mA | Power | P o | 1.1 mW linear characteristic |
| Maximum safe voltage | U m | 60 V (Attention! The rated voltage can be lower.) |
| Maximum safe voltage U m 60 V (Attention! The rated voltage can be lower.) | Maximum safe voltage | U m | 60 V (Attention! The rated voltage can be lower.) |
| Power | P o | 1.1 mW linear characteristic |
| Power dissipation | 0.4 W |
| Rated voltage | U r | 12 ... 35 V DC loop powered |
| Voltage | U o | 9.6 V |
| Voltage range | 0 ... 10 V , load ≥ 100 kΩ |
| AC and DC characteristics | |
| Rise time | 250 ms |
| Environment and package | |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Height 119 mm Width 20 mm Depth 115 mm | Height | 119 mm | Width | 20 mm | Depth | 115 mm |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Temperature effect | span: 0.050 % of span /K ; zero point: 0.060 % of span /K |
| Other | |
| After calibration | 0.1 % of full-scale value |
| Certificate | TÜV 01 ATEX 1777 X |
| Configuration | via DIP switches via potentiometer |
| Connection | terminals 1+, 2- |
| Connection side | field side |
| Control drawing | 116-0132 |
| Control drawing 116-0132 | Control drawing | 116-0132 |
| Control elements | DIP switch potentiometer |
| Degree of protection | IEC 60529:2001 |
| Depth | 115 mm |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
| EU-type examination certificate | ZELM 00 ATEX 0034 |
| Fault signal | downscaling ≤ 3 mA |
| Galvanic isolation | EN 50178:1997 |
| Input | EEx ia IIC |
| Input/Output | safe isolation according to EN 50178, rated insulation voltage 253 V eff |
| Labeling | space for labeling at the front |
| Linearization | ≤ 0.04 % of full-scale value |
| Load | (U -12 V) / 0.02 A |
| Marking | II (1)GD [EEx ia] IIC |
| Marking II 3G Ex nA II T4 | Marking | II 3G Ex nA II T4 |
| Mass | approx. 100 g |
| Signal type | Analog input |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Width | 20 mm |
Documents
No documents are linked to this part yet.