All alternatives

View full report

Technical parameters

Power
CurrentI o | 0.5 mA
Current output4 ... 20 mA , limited to ≤ 35 mA
Current range0 ... 20 mA , load ≤ 50 Ω
Influence of supply voltage6.5 ppm/V
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VInput/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Marking II (1)GD [EEx ia] IIC Input EEx ia IIC Voltage U o 9.6 V Current I o 0.5 mA Power P o 1.1 mW linear characteristicMarking | II (1)GD [EEx ia] IIC | Input | EEx ia IIC | Voltage | U o | 9.6 V | Current | I o | 0.5 mA | Power | P o | 1.1 mW linear characteristic
Maximum safe voltageU m | 60 V (Attention! The rated voltage can be lower.)
Maximum safe voltage U m 60 V (Attention! The rated voltage can be lower.)Maximum safe voltage | U m | 60 V (Attention! The rated voltage can be lower.)
PowerP o | 1.1 mW linear characteristic
Power dissipation0.4 W
Rated voltageU r | 12 ... 35 V DC loop powered
VoltageU o | 9.6 V
Voltage range0 ... 10 V , load ≥ 100 kΩ
AC and DC characteristics
Rise time250 ms
Environment and package
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Height 119 mm Width 20 mm Depth 115 mmHeight | 119 mm | Width | 20 mm | Depth | 115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Temperature effectspan: 0.050 % of span /K ; zero point: 0.060 % of span /K
Other
After calibration0.1 % of full-scale value
CertificateTÜV 01 ATEX 1777 X
Configurationvia DIP switches via potentiometer
Connectionterminals 1+, 2-
Connection sidefield side
Control drawing116-0132
Control drawing 116-0132Control drawing | 116-0132
Control elementsDIP switch potentiometer
Degree of protectionIEC 60529:2001
Depth115 mm
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
EU-type examination certificateZELM 00 ATEX 0034
Fault signaldownscaling ≤ 3 mA
Galvanic isolationEN 50178:1997
InputEEx ia IIC
Input/Outputsafe isolation according to EN 50178, rated insulation voltage 253 V eff
Labelingspace for labeling at the front
Linearization≤ 0.04 % of full-scale value
Load(U -12 V) / 0.02 A
MarkingII (1)GD [EEx ia] IIC
Marking II 3G Ex nA II T4Marking | II 3G Ex nA II T4
Massapprox. 100 g
Signal typeAnalog input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Width20 mm

Documents

No documents are linked to this part yet.