All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Measuring plate not detected ≥ 3 mA at nominal voltage Measuring plate detected ≤ 1 mA at nominal voltage | Measuring plate not detected | ≥ 3 mA at nominal voltage | Measuring plate detected | ≤ 1 mA at nominal voltage |
| Nominal voltage | U o | 8.2 V (R i approx. 1 kΩ) |
| Operating voltage | U B | 5 ... 25 V |
| AC and DC characteristics | |
| Switching frequency | f | 0 ... 100 Hz |
| Time delay before availability | t v | ≤ 1 ms |
| Environment and package | |
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Height | 99 mm |
| Height 99 mm Width 67 mm Length 34 mm | Height | 99 mm | Width | 67 mm | Length | 34 mm |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Other | |
| Actual operating distance | s r | 2.6 ... 2.6 mm typ. |
| Assured operating distance | s a | 0 ... 2.43 mm |
| Connection (system side) | screw terminals |
| Connection (valve side) | screw terminals |
| Core cross section (system side) | up to 2.5 mm 2 |
| Core cross section (valve side) | up to 2.5 mm 2 |
| Diagnostic Coverage (DC) | 0 % |
| Electromagnetic compatibility | NE 21:2007 |
| Equipment protection level Ga | IECEx TUN 17.0021X |
| Equipment protection level Ga IECEx TUN 17.0021X Equipment protection level Gb IECEx TUN 17.0021X Equipment protection level Mb IECEx TUN 17.0021X | Equipment protection level Ga | IECEx TUN 17.0021X | Equipment protection level Gb | IECEx TUN 17.0021X | Equipment protection level Mb | IECEx TUN 17.0021X |
| Equipment protection level Ga TÜV 99 ATEX 1479 X Equipment protection level Gb TÜV 99 ATEX 1479 X Equipment protection level Gc (ic) PF13CERT2895 X | Equipment protection level Ga | TÜV 99 ATEX 1479 X | Equipment protection level Gb | TÜV 99 ATEX 1479 X | Equipment protection level Gc (ic) | PF13CERT2895 X |
| Equipment protection level Gb | IECEx TUN 17.0021X |
| Equipment protection level Gc (ic) | PF13CERT2895 X |
| Equipment protection level Mb | IECEx TUN 17.0021X |
| Hazardous Location | 2020322315002262 |
| Hazardous Location 2020322315002262 | Hazardous Location | 2020322315002262 |
| Housing material | PBT |
| Hysteresis | H | typ. 5 % |
| Installation | flush mountable |
| Length | 34 mm |
| Mass | 91 g |
| Measuring plate detected | ≤ 1 mA at nominal voltage |
| Measuring plate not detected | ≥ 3 mA at nominal voltage |
| Mission Time (T M ) | 20 a |
| MTTF d | 834 a |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Electromagnetic compatibility NE 21:2007 Standards EN IEC 60947-5-2 | NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Electromagnetic compatibility | NE 21:2007 | Standards | EN IEC 60947-5-2 |
| NEPSI certificate | GYJ19.1410X |
| NEPSI certificate GYJ19.1410X | NEPSI certificate | GYJ19.1410X |
| Note | Installation in housing |
| Output type | NAMUR |
| Rated operating distance | s n | 3 mm |
| Reduction factor r 304 | 0.86 |
| Reduction factor r Al | 0.52 |
| Reduction factor r Brass | 0.54 |
| Reduction factor r Cu | 0.43 |
| Reduction factor r St37 | 1 |
| Reverse polarity protection | reverse polarity protected |
| Sensing face | PBT |
| Short-circuit protection | yes |
| Standards | EN IEC 60947-5-2 |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
| Switching function | 2 x normally closed (NC) |
| Switching state indicator | LED, yellow |
| Tightening torque, fastening screws | ≤ 0.3 Nm |
| Use in the hazardous area | see instruction manuals |
| Valve status indicator | LED, yellow can be switched off by of DB1 |
| Width | 67 mm |
Documents
No documents are linked to this part yet.