All alternatives

View full report

Technical parameters

Power
Measuring plate not detected ≥ 3 mA at nominal voltage Measuring plate detected ≤ 1 mA at nominal voltageMeasuring plate not detected | ≥ 3 mA at nominal voltage | Measuring plate detected | ≤ 1 mA at nominal voltage
Nominal voltageU o | 8.2 V (R i approx. 1 kΩ)
Operating voltageU B | 5 ... 25 V
AC and DC characteristics
Switching frequencyf | 0 ... 100 Hz
Time delay before availabilityt v | ≤ 1 ms
Environment and package
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Height99 mm
Height 99 mm Width 67 mm Length 34 mmHeight | 99 mm | Width | 67 mm | Length | 34 mm
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Other
Actual operating distances r | 2.6 ... 2.6 mm typ.
Assured operating distances a | 0 ... 2.43 mm
Connection (system side)screw terminals
Connection (valve side)screw terminals
Core cross section (system side)up to 2.5 mm 2
Core cross section (valve side)up to 2.5 mm 2
Diagnostic Coverage (DC)0 %
Electromagnetic compatibilityNE 21:2007
Equipment protection level GaIECEx TUN 17.0021X
Equipment protection level Ga IECEx TUN 17.0021X Equipment protection level Gb IECEx TUN 17.0021X Equipment protection level Mb IECEx TUN 17.0021XEquipment protection level Ga | IECEx TUN 17.0021X | Equipment protection level Gb | IECEx TUN 17.0021X | Equipment protection level Mb | IECEx TUN 17.0021X
Equipment protection level Ga TÜV 99 ATEX 1479 X Equipment protection level Gb TÜV 99 ATEX 1479 X Equipment protection level Gc (ic) PF13CERT2895 XEquipment protection level Ga | TÜV 99 ATEX 1479 X | Equipment protection level Gb | TÜV 99 ATEX 1479 X | Equipment protection level Gc (ic) | PF13CERT2895 X
Equipment protection level GbIECEx TUN 17.0021X
Equipment protection level Gc (ic)PF13CERT2895 X
Equipment protection level MbIECEx TUN 17.0021X
Hazardous Location2020322315002262
Hazardous Location 2020322315002262Hazardous Location | 2020322315002262
Housing materialPBT
HysteresisH | typ. 5 %
Installationflush mountable
Length34 mm
Mass91 g
Measuring plate detected≤ 1 mA at nominal voltage
Measuring plate not detected≥ 3 mA at nominal voltage
Mission Time (T M )20 a
MTTF d834 a
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Electromagnetic compatibility NE 21:2007 Standards EN IEC 60947-5-2NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Electromagnetic compatibility | NE 21:2007 | Standards | EN IEC 60947-5-2
NEPSI certificateGYJ19.1410X
NEPSI certificate GYJ19.1410XNEPSI certificate | GYJ19.1410X
NoteInstallation in housing
Output typeNAMUR
Rated operating distances n | 3 mm
Reduction factor r 3040.86
Reduction factor r Al0.52
Reduction factor r Brass0.54
Reduction factor r Cu0.43
Reduction factor r St371
Reverse polarity protectionreverse polarity protected
Sensing facePBT
Short-circuit protectionyes
StandardsEN IEC 60947-5-2
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Switching function2 x normally closed (NC)
Switching state indicatorLED, yellow
Tightening torque, fastening screws≤ 0.3 Nm
Use in the hazardous areasee instruction manuals
Valve status indicatorLED, yellow can be switched off by of DB1
Width67 mm

Documents

No documents are linked to this part yet.