All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Insulation voltage | U i | ≥ 500 V |
| LED POWER | voltage ON; LED green |
| Power supply | max. 4 A per AS-Interface circuit |
| Rated operating current | I e | approx. 250 mA |
| Rated operating voltage | U e | 24 V DC ( 20 ... 31.6 V ) safe isolated power supplies (PELV) Note 24 V power supply, max. segment length: 50 m Supply via AS-Interface power supply, max. segment length: 100 m |
| Environment and package | |
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) |
| Height | 120 mm |
| Height 120 mm Width 75 mm Length 83 mm | Height | 120 mm | Width | 75 mm | Length | 83 mm |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Other | |
| AS-Interface | spring terminals, removable |
| AS-Interface specification | V3.0 |
| Button MODE | Mode selection PRJ-operation/save configuration/cursor |
| Construction type | Low profile housing , Stainless steel |
| Data decoupling | integrated |
| Degree of protection | EN 60529:2000 |
| Diagnostics function | Extended function via display |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Display | Illuminated graphical LC display for addressing and error messages |
| Duplicate address detection | from AS-Interface slaves |
| Earth fault detection | EFD | integrated |
| Electromagnetic compatibility | EN 61326:2003 |
| EMC monitoring | integrated |
| ESC button | Mode selection traditional-graphical/cancel |
| Interface type | RS-485 |
| LED AS-i ACTIVE | AS-Interface operation normal; LED green |
| LED CONFIG ERR | configuration error; LED red |
| LED PRG ENABLE | autom. programming; LED green |
| LED PRJ MODE | projecting mode active; LED yellow |
| LED PROFIBUS | PROFIBUS communication active; LED green |
| LED U AS-i | AS-Interface voltage; LED green |
| Length | 83 mm |
| Mass | 500 g |
| MTTF d | 105 a at 30 °C |
| OK button | Mode selection traditional-graphical/confirmation |
| PLC-Functionality | activateable |
| PROFIBUS | Sub-D interface |
| Protocol | PROFIBUS DP V1 |
| Shock resistance | EN 61131-2:2004 |
| Switch SET | Selection and setting of a slave address |
| Transfer rate | 9.6 kBit/s / 12 MBit/s , Automatic baud rate detection |
| UL approval | An isolated source with a secondary open circuit voltage of ≤ 30 V DC with a 3 A maximum over current protection. Over current protection is not required when a Class 2 source is employed. UL mark does not provide UL certification for any functional safety rating or aspects of the device. |
| UL File Number | E223772 only from low voltage, limited energy source (SELV or PELV) or listed Class 2 source |
| Width | 75 mm |
Documents
No documents are linked to this part yet.