| Power | |
|---|---|
| Auxiliary voltage (input) | U EXT | 12 ... 30 V DC PELV |
| Auxiliary voltage (output) | U AUX | 20 ... 30 V DC PELV |
| Current | 2 A Per output, total 4 A (T B ≤ 60 °C) 1 A Per output, total 4 A (T B ≤ 70 °C) |
| Current loading capacity | ≤ 150 mA, overload- and short-circuit protected (INT) |
| Input current | ≤ 5.6 mA (max.) |
| Pulse withstand voltage | 0.8 kV |
| Rated insulation voltage | 92 V |
| Rated operating current | I e | ≤ 35 mA (without sensors) / max. 190 mA |
| Rated operating voltage | U e | 26.5 ... 31.6 V from AS-Interface |
| Supply | from AS-Interface (switch position INT, default settings) or external U EXT (switch position EXT) |
| Voltage | 21 ... 31 V DC (INT) |
| AC and DC characteristics | |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Signal delay | < 1 ms (input/AS-Interface) |
| Environment and package | |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Height | 100 mm |
| Height 100 mm Width 18.9 mm Length 124 mm | Height | 100 mm | Width | 18.9 mm | Length | 124 mm |
| Mounting | DIN mounting rail |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Other | |
| 0 (unattenuated) | ≤ 0.5 mA |
| 0 (unattenuated) ≤ 0.5 mA 1 (attenuated) ≥ 2 mA | 0 (unattenuated) | ≤ 0.5 mA | 1 (attenuated) | ≥ 2 mA |
| 1 (attenuated) | ≥ 2 mA |
| Altitude | ≤ 2000 m above MSL |
| AS-Interface | EN 62026-2:2013 |
| AS-Interface specification | V3.0 |
| Climatic conditions | For indoor use only |
| Connection | Removable push-in terminals rated connection capacity: rigid: 0.20 mm 2 ... 1.5 mm 2 flexible (without wire end ferrule): 0.20 mm 2 ... 2.5 mm 2 flexible (with wire end ferrule): 0.25 mm 2 ... 1.5 mm 2 |
| D0 | IN1 O1 |
| D0 IN1 O1 D1 IN2 O2 D2 IN3 O3 D3 IN4 O4 | D0 | IN1 O1 | D1 | IN2 O2 | D2 | IN3 O3 | D3 | IN4 O4 |
| D1 | IN2 O2 |
| D2 | IN3 O3 |
| D3 | IN4 O4 |
| Data bits (function via AS-Interface) | Input Output |
| Degree of protection | EN 60529:2000 |
| Directive 2006/42/EC | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
| Directive 2006/42/EC EN ISO 13849-1:2008 EN ISO 13849-2:2012 | Directive 2006/42/EC | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Electrical safety | IEC 61140:2009 |
| Emitted interference | EN 61000-6-4:2007 |
| Fieldbus standard | EN 62026-2:2013 |
| Functional safety | EN ISO 13849-1:2008 EN ISO 13849-2:2012 |
| Housing | PA 66-FR |
| Housing PA 66-FR | Housing | PA 66-FR |
| ID1 code | 7 |
| ID2 code | 7 |
| ID code | A |
| Input | EN 61131-2:2004 |
| IO code | 7 |
| LED AUX | ext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage |
| LED FAULT | Error display; red LED red: communication error, i.e. address is 0 red flashing: overload internal input supply, i.e. overload or lead interruption outputs |
| LED IN | switching state (input); 4 LED yellow |
| LED INT | Internal input supply active; LED green |
| LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
| LED PWR | AS-Interface voltage; green LED green: voltage OK flashing green: address 0 |
| Length | 124 mm |
| Mass | 110 g |
| MTBF | 141 a |
| Node type | A/B node |
| Number/Type | 4 inputs for 3-wire sensors (PNP), DC |
| P0 | Communication monitoring P0 = 0 monitoring = off, the outputs maintain the status if communication fails P0 = 1 monitoring = on, i.e. if communication fails, the outputs are deenergised (default settings) |
| P1 | Input filter P1 = 0 input filter on, pulse suppression ≤ 2 ms P1 = 1 input filter off (default settings) |
| P2 | Lead breakage outputs P2 = 0 lead breakage on P2 = 1 lead breakage off (default settings) |
| P3 | not used |
| Parameter bits (programmable via AS-i) | function |
| Pollution degree | 2 |
| Profile | S-7.A.7 |
| Protection class | III |
| Relative humidity | 85 % , non-condensing |
| Required gateway specification | ≥ V3.0 |
| Shock and impact resistance | 15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks |
| Surge protection | U EXT , U AUX , U e : overvoltage category II, safe isolated power supplies (PELV) Overvoltage category of the power supplies (primary): III |
| Switching point | according to DIN EN 61131-2 (type 1) |
| UL File Number | E223772 |
| Usage category | DC-13 |
| Vibration resistance | 0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
| Width | 18.9 mm |