Pepperl+Fuchs, Inc.Germany
53061
ActiveSurge protector, pluggable module for spur installation on segment protector
All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Current | I i | 500 mA |
| Marking II 1G Ex ia IIC T4 Voltage U i 24 V Current I i 500 mA Internal capacitance C i 2 nF Internal inductance L i 0.1 µH | Marking | II 1G Ex ia IIC T4 | Voltage | U i | 24 V | Current | I i | 500 mA | Internal capacitance | C i | 2 nF | Internal inductance | L i | 0.1 µH |
| Marking II 3G Ex nAc IIC T4 , [exsign] II 3G Ex ic IIC T4 Voltage U i 33 V Current I i 600 mA Internal capacitance C i 2 nF Internal inductance L i 0.1 µH | Marking | II 3G Ex nAc IIC T4 , [exsign] II 3G Ex ic IIC T4 | Voltage | U i | 33 V | Current | I i | 600 mA | Internal capacitance | C i | 2 nF | Internal inductance | L i | 0.1 µH |
| Rated current | I r | 250 mA |
| Rated voltage | U r | 36 V |
| Self current consumption | max. 6 mA (for version SCP-LBF-IA1.36.IE.1) , max. 0 mA (for version SCP-LBF-IA1.36.IE.0) |
| Voltage | U i | 24 V |
| Voltage protection level | U p |
| Environment and package | |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Design / Mounting | Cabinet installation |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Other | |
| Approved for | Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 1, Ex ia IIC T4 Class I, Zone 2, Ex ic IIC T4 Class I, Zone 1, AEx ia IIC T4 Class I, Zone 2, AEx ic IIC T4 Class I, Division 2, Groups A, B, C, D T4 Class I, Zone 2, Ex nL IIC T4 Class I, Zone 2, Ex nA IIC T4 Class I, Zone 2, AEx nAc IIC T4 |
| Certificate | SIRA 12 ATEX 4176X |
| Climatic conditions | IEC 60721 |
| Connection type | screw terminals |
| Control drawing | 116-0365 |
| Core cross section | flexible wire 2.5 mm 2 solid wire max. 4 mm 2 |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
| CSA approval | CoC 2595441 |
| Degree of protection | IEC 60529 |
| Directive 2014/30/EU | EN 61326-1:2013 |
| Directive 2014/30/EU EN 61326-1:2013 | Directive 2014/30/EU | EN 61326-1:2013 |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
| Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 | Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
| Electromagnetic compatibility | NAMUR NE 21 |
| EU-type examination certificate | SIRA 12 ATEX 2128X |
| Fieldbus standard | IEC 61158-2 |
| Grounding | M4 screw and external grounding rail |
| Housing material | Polyamide PA 6.6 |
| IECEx certificate | IECEx SIR 12.0051X |
| IECEx certificate IECEx SIR 12.0051X IECEx marking Ex ia IIC T4 Ex ic IIC T4 Ex nAc IIC T4 | IECEx certificate | IECEx SIR 12.0051X | IECEx marking | Ex ia IIC T4 Ex ic IIC T4 Ex nAc IIC T4 |
| IECEx marking | Ex ia IIC T4 Ex ic IIC T4 Ex nAc IIC T4 |
| Installation in hazardous area | Zone 1 / Div. 1 |
| Internal capacitance | C i | 2 nF |
| Internal inductance | L i | 0.1 µH |
| LED ERR | green flashing: status OK , red flashing: maintenance required (for version SCP-LBF-IA1.36.IE.1) |
| Line/Earth | max. 980 V category B2 10/700 µsec , 50 A per line max. 800 V category C1 8/20 µsec , 50 A per line max. 1450 V category C2 8/20 µsec , 5 kA per line max. 1200 V category C3 1 kV/µsec , 50 A per line max. 980 V category D1 10/350 µsec , 500 A per line |
| Line/Line | max. 50 V category B2 10/700 µsec , 25 A max. 53 V category C1 8/20 µsec , 150 A max. 55 V category C2 8/20 µsec , 150 A max. 46 V category C3 1 kV/µsec , 10 A |
| Line/Line max. 1 ns Line/Earth max. 100 ns Screen/Shield-Earth max. 100 ns | Line/Line | max. 1 ns | Line/Earth | max. 100 ns | Screen/Shield-Earth | max. 100 ns |
| Marking | II 1G Ex ia IIC T4 |
| Mass | 45 g |
| Overstressed fault mode | according IEC 61643-21 line inoperable mode 2 |
| Per line | 5 kA category C2 8/20 µsec |
| Per line 5 kA category C2 8/20 µsec Screen/Shield indirectly grounded (via GDT) 1 kA category D1 10/350 µsec 10 kA category C2 8/20 µsec | Per line | 5 kA category C2 8/20 µsec | Screen/Shield indirectly grounded (via GDT) | 1 kA category D1 10/350 µsec 10 kA category C2 8/20 µsec |
| Reaction time | t A |
| Relative humidity | ≤ 95 % non-condensing |
| Screen/Shield-Earth | max. 100 ns |
| Screen/Shield indirectly grounded (via GDT) | max. 500 V category B2 10/700 µsec , 100 A max. 600 V category C1 8/20 µsec , 500 A max. 700 V category C2 8/20 µsec , 10 kA max. 550 V category C3 1 kV/µsec , 100 A max. 570 V category D1 10/350 µsec , 1 kA |
| Shock resistance | EN 60068-2-27 |
| Supplementary information | FISCO field device |
| Surge protection | IEC 61643-21 |
| Vibration resistance | EN 60068-2-6 |
Documents