All alternatives

View full report

Technical parameters

Power
Auxiliary voltage (output)U AUX | 24 V DC ± 15 % PELV
Current loading capacity≤ 120 mA (signal current + actuator supply) from AS-Interface; overload and short-circuit protected ≤ 700 mA (signal current + actuator supply) from external bulk power supply U AUX , overload and short-circuit protected
Rated operating currentI e | ≤ 75 mA (without outputs) / max. 200 mA
Rated operating voltageU e | 26.5 ... 31.6 V from AS-Interface
Short-circuit currentvoltage output: max. 22 mA
Supplyfrom AS-Interface (switch position INT, default settings) or auxiliary voltage U EXT (switch position EXT)
AC and DC characteristics
Accuracy0.15 % of full-scale value
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
ResolutionVoltage output: 3 mV Current output: 6 µA
Environment and package
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Height35 mm
Height 35 mm Diameter 85 mmHeight | 35 mm | Diameter | 85 mm
Housing PBT PC Mounting screw Stainless steel 1.4305 / AISI 303Housing | PBT PC | Mounting screw | Stainless steel 1.4305 / AISI 303
MountingMounting plate
Mounting screwStainless steel 1.4305 / AISI 303
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Temperature influence1 µA/K or 0,3 mV/K
Other
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Climatic conditionsFor indoor use only
ConnectionAS-Interface/U AUX : cable piercing method, flat cable yellow/flat cable black Outputs: M12 round connector
Degree of protectionEN 60529:2000
Diameter85 mm
Directive 2014/30/EUEN 62026-2:2013
Directive 2014/30/EU EN 62026-2:2013Directive 2014/30/EU | EN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPBT PC
ID1 codeF
ID2 code6
ID code3
IO code7
IO code 7 ID code 3 ID1 code F ID2 code 6IO code | 7 | ID code | 3 | ID1 code | F | ID2 code | 6
LED ANALOGStatus of output signal; yellow LED Yellow: Output value within range Yellow flashing: lead breakage (on current output) or output value out of range
LED AS-i/FAULTStatus display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault
LED AUXext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage
LED INT/EXTstatus display output supply; LED green green: output supply from AS-Interface off: output supply from auxiliary voltage
Loadvoltage output: min. 1 kΩ current output: max. 600 Ω
Mass200 g
Node typeStandard node
Number/Type4 analog outputs Current: 0 ... 20 mA Voltage: 0 ... 10 V
Pollution degree3
ProfileS-7.3.6
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Surge protectionU AUX , U in : Over voltage category III, safe isolated power supplies (PELV)
Tightening torque, cable gland0.4 Nm
Tightening torque, housing screws1.8 Nm
UL File NumberE223772

Documents

No documents are linked to this part yet.