All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Rated operating current | I e | ≤ 100 mA |
| Rated operating voltage | U e | 26.5 ... 31.6 V from AS-Interface |
| Supply | from AS-Interface |
| AC and DC characteristics | |
| Accuracy | 0.15 % of full-scale value |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008 |
| Resolution | 6 µA |
| Environment and package | |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Height | 35 mm |
| Height 35 mm Diameter 85 mm | Height | 35 mm | Diameter | 85 mm |
| Housing PBT PC Mounting screw Stainless steel 1.4305 / AISI 303 | Housing | PBT PC | Mounting screw | Stainless steel 1.4305 / AISI 303 |
| Mounting | Mounting plate |
| Mounting screw | Stainless steel 1.4305 / AISI 303 |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Temperature influence | 1 µA/K |
| Other | |
| Altitude | ≤ 2000 m above MSL |
| AS-Interface | EN 62026-2:2013 |
| AS-Interface specification | V3.0 |
| Climatic conditions | For indoor use only |
| Connection | AS-Interface: M12 round connector Outputs: M12 round connector |
| Degree of protection | EN 60529:2000 |
| Diameter | 85 mm |
| Directive 2014/30/EU | EN 62026-2:2013 |
| Directive 2014/30/EU EN 62026-2:2013 | Directive 2014/30/EU | EN 62026-2:2013 |
| Emitted interference | EN 61000-6-4:2007 |
| Fieldbus standard | EN 62026-2:2013 |
| Housing | PBT PC |
| ID1 code | F |
| ID2 code | 5 |
| ID code | 3 |
| IO code | 7 |
| IO code 7 ID code 3 ID1 code F ID2 code 5 | IO code | 7 | ID code | 3 | ID1 code | F | ID2 code | 5 |
| LED ANALOG | Status of output signal; yellow LED Yellow: 0 mA ≤ I ≤ 23 mA Yellow flashing: lead breakage or I > 23 mA |
| LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
| Load | max. 600 Ω |
| Mass | 200 g |
| Node type | Standard node |
| Number/Type | 2 analog outputs (current), 0 ... 20 mA |
| Pollution degree | 3 |
| Profile | S-7.3.5 |
| Protection class | III |
| Relative humidity | 85 % , non-condensing |
| Required gateway specification | ≥ V2.1 |
| Surge protection | U e : Over voltage category III, safe isolated power supplies (PELV) |
| Tightening torque, cable gland | 0.4 Nm |
| Tightening torque, housing screws | 1.8 Nm |
| UL File Number | E223772 |
Documents
No documents are linked to this part yet.