All alternatives

View full report

Technical parameters

Power
CurrentI o | 17.1 mA
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Maximum safe voltageU m | 253 V AC (Attention! U m is no rated voltage.)
Maximum safe voltage U m 253 V AC (Attention! U m is no rated voltage.)Maximum safe voltage | U m | 253 V AC (Attention! U m is no rated voltage.)
Open circuit voltage/short-circuit currentapprox. 10 V DC / approx. 8 mA
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 V eff
PowerP o | 45 mW (linear characteristic)
Power consumption≤ 600 mW
Power dissipation≤ 500 mW
Rated currentI r | ≤ 25 mA
Rated voltageU r | 19 ... 30 V DC bus powered via Termination Board
VoltageU o | 10.5 V
AC and DC characteristics
Protection against electrical shockIEC 61010-1
Ripple≤ 10 %
Switching frequency≤ 5 kHz
Environment and package
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Mountingon termination board
Other
CertificateKIWA 15 ATEX 0037 X
Codingpin 1 and 2 trimmed For further information see system description.
Configurationvia DIP switches
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Connection sidefield side
Control drawing116-0430 (cFMus)
Control drawing 116-0331Control drawing | 116-0331
Control drawing 116-0430 (cFMus)Control drawing | 116-0430 (cFMus)
Control elementsDIP switch
Degree of protectionIEC 60529:2001
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 , EN 50303:2000
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 , EN 50303:2000Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-7:2015+A1:2018 , EN 50303:2000
Display elementsLEDs
Electromagnetic compatibilityEN IEC 61326-3-2:2018 , NE 21:2017 For further information see system description.
EU-type examination certificateBVS 11 ATEX E 026
IECEx certificateIECEx BVS 11.0040 IECEx KIWA 15.0019X
IECEx certificate IECEx BVS 11.0040 IECEx KIWA 15.0019X IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I , Ex ec IIC T4 GcIECEx certificate | IECEx BVS 11.0040 IECEx KIWA 15.0019X | IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I , Ex ec IIC T4 Gc
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I , Ex ec IIC T4 Gc
InputEx ia
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Labelingspace for labeling at the front
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Marking II 3G Ex ec IIC T4 GcMarking | II 3G Ex ec IIC T4 Gc
Massapprox. 90 g
Output I, IIsignal or fault message, passive transistor output (resistive) 0-signal: 15 kΩ ± 5 % 1-signal: 5 kΩ ± 5 % fault: > 100 kΩ
Output/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 V eff
Output typeopen collector transistor (internal fault bus)
Pulse/Pause ratiomin. 100 µs / min. 100 µs
Rated valuesacc. to EN 60947-5-6 (NAMUR), see manual for electrical data
Response time≤ 200 µs
Safety Integrity Level (SIL)SIL 2
Signal typeDigital Input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Systematic capability (SC)SC 3
UL approvalE106378

Documents

No documents are linked to this part yet.