All alternatives

View full report

Technical parameters

Power
Current loading capacity≤ 200 mA, overload and short-circuit protected
Input current≤ 9 mA (limited internally)
Rated operating currentI e | ≤ 40 mA (without sensors) / max. 240 mA
Rated operating voltageU e | 18,0 ... 31.6 V from AS-Interface
Supplyfrom AS-Interface
Voltage12 ... 31 V
AC and DC characteristics
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Signal delay< 1 ms (input/AS-Interface)
Environment and package
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Height35 mm
Height 35 mm Diameter 85 mmHeight | 35 mm | Diameter | 85 mm
Housing PBT PC Mounting screw Stainless steel 1.4305 / AISI 303Housing | PBT PC | Mounting screw | Stainless steel 1.4305 / AISI 303
MountingMounting plate
Mounting screwStainless steel 1.4305 / AISI 303
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Other
0 (unattenuated)≤ 3 mA
0 (unattenuated) ≤ 3 mA 1 (attenuated) ≥ 5 mA0 (unattenuated) | ≤ 3 mA | 1 (attenuated) | ≥ 5 mA
1 (attenuated)≥ 5 mA
Altitude≤ 2000 m above MSL
AS-InterfaceEN 62026-2:2013
AS-Interface specificationV3.0
Climatic conditionsFor indoor use only
ConnectionAS-Interface: AS-Interface flat cable Inputs: M12 round connector
Degree of protectionEN 60529:2000
Diameter85 mm
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007
Emitted interferenceEN 61000-6-4:2007
Fieldbus standardEN 62026-2:2013
HousingPBT PC
ID1 code7
ID2 code2
ID codeA
InputEN 61131-2:2007
IO code0
IO code 0 ID code A ID1 code 7 ID2 code 2IO code | 0 | ID code | A | ID1 code | 7 | ID2 code | 2
LED AS-i/FAULTStatus display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply overload
LED INswitching state (input); 4 LED yellow
Mass200 g
Node typeA/B node
Number/Type4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC
Pollution degree3
ProfileS-0.A.2
Protection classIII
Relative humidity85 % , non-condensing
Required gateway specification≥ V2.1
Shock and impact resistance30 g , 11 ms in 6 spatial directions 3 shocks 10 g , 16 ms in 6 spatial directions 1000 shocks
Surge protectionU e : Over voltage category III, safe isolated power supplies (PELV)
Switching pointaccording to DIN EN 61131-2 (Type 2)
Tightening torque, cable gland0.4 Nm
Tightening torque, housing screws1.8 Nm
UL File NumberE223772
Vibration resistance0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles

Documents