All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Auxiliary voltage (output) | U AUX | 20 ... 30 V DC PELV |
| Current | 2 A per output TB ≤ 40 °C: 6 A total TB ≤ 70 °C: sum O1 + O2 max. 2 A, sum O3 + O4 max. 2 A |
| Current loading capacity | ≤ 200 mA, overload and short-circuit protected |
| Input current | ≤ 9 mA (limited internally) |
| Rated operating current | I e | ≤ 40 mA (without sensors) / max. 240 mA |
| Rated operating voltage | U e | 18,0 ... 31.6 V from AS-Interface |
| Supply | from AS-Interface |
| Voltage | 12 ... 31 V |
| AC and DC characteristics | |
| Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013 |
| Signal delay | < 1 ms (input/AS-Interface) |
| Environment and package | |
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Height | 35 mm |
| Height 35 mm Diameter 85 mm | Height | 35 mm | Diameter | 85 mm |
| Housing PBT PC Mounting screw Stainless steel 1.4305 / AISI 303 | Housing | PBT PC | Mounting screw | Stainless steel 1.4305 / AISI 303 |
| Mounting | Mounting plate |
| Mounting screw | Stainless steel 1.4305 / AISI 303 |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Other | |
| 0 (unattenuated) | ≤ 3 mA |
| 0 (unattenuated) ≤ 3 mA 1 (attenuated) ≥ 5 mA | 0 (unattenuated) | ≤ 3 mA | 1 (attenuated) | ≥ 5 mA |
| 1 (attenuated) | ≥ 5 mA |
| Altitude | ≤ 2000 m above MSL |
| AS-Interface | EN 62026-2:2013 |
| AS-Interface specification | V3.0 |
| Climatic conditions | For indoor use only |
| Connection | AS-Interface/U AUX : AS-Interface flat cable Inputs/outputs: M12 round connector |
| Degree of protection | EN 60529:2000 |
| Diameter | 85 mm |
| Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Directive 2014/30/EU EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 | Directive 2014/30/EU | EN 62026-2:2013 EN 61000-6-2:2005, EN 61000-6-4:2007 |
| Emitted interference | EN 61000-6-4:2007 |
| Fieldbus standard | EN 62026-2:2013 |
| Housing | PBT PC |
| ID1 code | 7 |
| ID2 code | 7 |
| ID code | A |
| Input | EN 61131-2:2007 |
| Input/Output | safe isolation, rated insulation voltage 40 V DC |
| IO code | 7 |
| IO code 7 ID code A ID1 code 7 ID2 code 7 | IO code | 7 | ID code | A | ID1 code | 7 | ID2 code | 7 |
| LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: sensor supply i.e. overload or lead interruption outputs |
| LED AUX | ext. auxiliary voltage U AUX ; dual LED green/red green: voltage OK red: reverse voltage |
| LED IN | switching state (input); 4 LED yellow |
| LED OUT | switching state (output); 4 LED yellow/red yellow: output active red: output overload or lead interruption |
| Mass | 200 g |
| Node type | A/B node |
| Number/Type | 4 inputs for 2- or 3-wire sensors (PNP), DC option 2 inputs for 4-wire sensors (PNP), DC |
| Output/AS-Interface | safe isolation, rated insulation voltage 40 V DC |
| Pollution degree | 3 |
| Profile | S-7.A.7 |
| Protection class | III |
| Relative humidity | 85 % , non-condensing |
| Required gateway specification | ≥ V3.0 |
| Shock and impact resistance | 30 g , 11 ms in 6 spatial directions 3 shocks 10 g , 16 ms in 6 spatial directions 1000 shocks |
| Surge protection | U AUX , U in : Over voltage category III, safe isolated power supplies (PELV) |
| Switching point | according to DIN EN 61131-2 (Type 2) |
| Tightening torque, cable gland | 0.4 Nm |
| Tightening torque, housing screws | 1.8 Nm |
| UL File Number | E223772 |
| Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles |
Documents