All alternatives

View full report

Technical parameters

Power
No-load supply currentI 0 | ≤ 15 mA
Off-state currentI r | 0 ... 0.01 mA typ. 0.1 µA at 25 °C
Operating currentI L | 0 ... 250 mA
Operating voltageU B | 10 ... 30 V DC
Rated impulse withstand voltageU imp | 800 V
Rated insulation voltageU i | 60 V
Rated insulation voltage U i 60 V Rated impulse withstand voltage U imp 800 VRated insulation voltage | U i | 60 V | Rated impulse withstand voltage | U imp | 800 V
Voltage dropU d | ≤ 2.5 V
AC and DC characteristics
Switching frequencyf | 0 ... 1400 Hz
Environment and package
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Height40 mm
Height 40 mm Width 12 mm Length 26 mmHeight | 40 mm | Width | 12 mm | Length | 26 mm
Other
Assured operating distances a | 0 ... 6.48 mm
Bending radius> 10 x cable diameter
Cable diameter5.2 mm ± 0.2 mm
CCC approvalCCC approval / marking not required for products rated ≤36 V
Colorgrey
Connection typecable
Core cross section0.5 mm 2
Degree of protectionIP67
Diagnostic Coverage (DC)0 %
Housing materialPA
HysteresisH | typ. 5%
Installationnon-flush
LengthL | 2 m
MaterialPVC
Mission Time (T M )20 a
MTTF d1640 a
Number of cores4
Output polarityDC
Output typePNP
Protection classII
Rated operating distances n | 8 mm
Reduction factor r 3040.7
Reduction factor r Al0.45
Reduction factor r Brass0.55
Reduction factor r Cu0.45
Reverse polarity protectionreverse polarity protected
Sensing facePA
Short-circuit protectionpulsing
StandardsEN IEC 60947-5-2
Standards EN IEC 60947-5-2Standards | EN IEC 60947-5-2
Switching functioncomplementary
Switching state indicatorLED, yellow
Tightening torque, fastening screwsThreading M3 ≤ 1.1 Nm
UL approvalcULus Listed Load Type: Resistive Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 30 V DC Output Switching Current: 250 mA
Width12 mm
Wire end ferrulesyes

Documents