Pepperl+Fuchs, Inc.Germany
27689
ActiveAdvanced diagnostic module, plug-in module for the fieldbus power hub
All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Fieldbus segment/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 V eff |
| Power dissipation | max. 2 W |
| Rated current | I r | 110 ... 30 mA |
| Rated voltage | U r | 19.2 ... 35 V |
| Environment and package | |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Design / Mounting | Motherboard based |
| Height | 106 mm |
| Height 106 mm Width 18 mm Depth 128 mm | Height | 106 mm | Width | 18 mm | Depth | 128 mm |
| Mounting | motherboard mounting |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Other | |
| Certificate | TÜV 04 ATEX 2500 X |
| Core cross section | motherboard specific |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
| Degree of protection | IEC 60529 |
| Depth | 128 mm |
| DIP switch | diagnostic address 1...247, binary coded |
| Directive 2014/30/EU | EN 61326-1:2013 |
| Directive 2014/30/EU EN 61326-1:2013 | Directive 2014/30/EU | EN 61326-1:2013 |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
| Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 | Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
| Electromagnetic compatibility | NE 21:2011 |
| Fault signal | VFC alarm 1 A, 50 V DC, normally closed |
| Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 V eff |
| Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA |
| FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X |
| FM certificate FM 19 US 0015 X and FM 19 CA 0011 X FM marking Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex ec IIC T4 | FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X | FM marking | Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex ec IIC T4 |
| FM marking | Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex ec IIC T4 |
| Housing material | Polycarbonate |
| IECEx certificate | IECEx TUN 13.0038X |
| IECEx certificate IECEx TUN 13.0038X IECEx marking Ex nA IIC T4 Gc | IECEx certificate | IECEx TUN 13.0038X | IECEx marking | Ex nA IIC T4 Gc |
| IECEx marking | Ex nA IIC T4 Gc |
| Installation in hazardous area | Zone 2 / Div. 2 |
| Interface type | diagnostic bus: RS 485 |
| LED PRI PWR | green: on, primary bulk power supply connected |
| LED SEC PWR | green: on, secondary bulk power supply connected |
| LED Seg 1...4 | yellow: bus activity; red 2 Hz flashing: alarm; red: hardware error |
| Marking | II 3 G Ex nA IIC T4 Gc |
| Marking II 3 G Ex nA IIC T4 Gc | Marking | II 3 G Ex nA IIC T4 Gc |
| Mass | approx. 100 g |
| Mating cycles | 100 |
| Number of segments | 4 |
| Patents | This product may be covered by the following patent: US7,698,103 |
| Pollution degree | max. 2, according to IEC 60664 |
| Relative humidity | < 95 % non-condensing |
| Shock resistance | EN 60068-2-27 |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Vibration resistance | EN 60068-2-6 |
| Width | 18 mm |
Documents
No documents are linked to this part yet.