All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Auxiliary voltage (output) | U AUX | 20 ... 30 V DC PELV |
| Current | 1 A per output , 2 A per module |
| Current loading capacity | 2 A (I AUX ) |
| Input current | 3 mA (typically) |
| Rated operating current | I e | ≤ 30 mA |
| Rated operating voltage | U e | 26.5 ... 31.6 V from AS-Interface |
| Supply | from external auxiliary voltage U AUX |
| Voltage | ≥ (U AUX - 0.5 V) |
| AC and DC characteristics | |
| Noise immunity | EN 61326-1:2006 |
| Signal delay | < 2 ms (input/AS-Interface) |
| Signal frequency | ≤ 250 Hz |
| Environment and package | |
| Ambient temperature | -25 ... 60 °C (-13 ... 140 °F) |
| Mounting | Mounting plate |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Other | |
| 0 (unattenuated) | ≤ 0.5 mA |
| 0 (unattenuated) ≤ 0.5 mA 1 (attenuated) ≥ 2 mA | 0 (unattenuated) | ≤ 0.5 mA | 1 (attenuated) | ≥ 2 mA |
| 1 (attenuated) | ≥ 2 mA |
| Altitude | ≤ 2000 m above MSL |
| AS-Interface | EN 62026-2:2013 |
| AS-Interface specification | V2.1 |
| Climatic conditions | For indoor use only |
| Connection | Cable piercing method flat cable yellow/flat cable black inputs/outputs: M12 round connector |
| D0 | IN1 O1 |
| D0 IN1 O1 D1 IN2 O2 D2 IN3 - D3 IN4 - | D0 | IN1 O1 | D1 | IN2 O2 | D2 | IN3 - | D3 | IN4 - |
| D1 | IN2 O2 |
| D2 | IN3 - |
| D3 | IN4 - |
| Data bits (function via AS-Interface) | Input Output |
| Degree of protection | EN 60529:2000 |
| Directive 2014/30/EU | EN 62026-2:2013 |
| Directive 2014/30/EU EN 62026-2:2013 | Directive 2014/30/EU | EN 62026-2:2013 |
| Electromagnetic compatibility | observe notices on the certificate of conformity. |
| Emitted interference | EN 61000-6-4:2001 |
| Galvanic isolation | EN 60947-1:2007 |
| Housing | PBT |
| Housing PBT | Housing | PBT |
| ID1 code | 7 |
| ID2 code | E |
| ID code | A |
| Input | EN 61131-2:2007 |
| Input/AS-Interface | Basic insulation, rated insulation voltage 120 V DC |
| Input/Output | none |
| IO code | 7 |
| LED AUX | ext. auxiliary voltage U AUX ; LED green |
| LED FAULT | error display; LED red red: communication error or address is 0 red flashing: overload of outputs |
| LED IN | switching state (input); 4 LED yellow |
| LED OUT | Switching state (output); 2 LED yellow |
| LED PWR | AS-Interface voltage; LED green |
| Mass | approx. 100 g |
| Mech. capacity | EN 60068-2-6:2008, EN 60068-2-27:1995 |
| Node type | A/B node |
| Number/Type | 4 inputs for mechanical contacts or 3-wire sensors (PNP), DC |
| Output/AS-Interface | Basic insulation, rated insulation voltage 120 V DC |
| P0 | not used |
| P0 not used P1 not used P2 not used P3 not used | P0 | not used | P1 | not used | P2 | not used | P3 | not used |
| P1 | not used |
| P2 | not used |
| P3 | not used |
| Parameter bits (programmable via AS-i) | function |
| Pollution degree | 3 |
| Profile | S-7.A.E |
| Protection class | III |
| Relative humidity | 85 % , non-condensing |
| Required gateway specification | ≥ V2.1 |
| Surge protection | U AUX , U in : Over voltage category III, safe isolated power supplies (PELV) |
| Switching point | according to DIN EN 61131-2 (type 1) |
| Tightening torque, cable gland | 0.4 Nm |
| UL File Number | E223772 |
| Usage category | DC-13 |
Documents
No documents are linked to this part yet.