All alternatives

View full report

Technical parameters

Power
Current I o13.1 mA
Current range0 ... 20 mA or 4 ... 20 mA
Influence of supply voltage< 0.01 % of span
Input/Other circuits safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 VInput/Other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Maximum safe voltageU m | 250 V (Attention! This is not the rated voltage.)
Maximum safe voltage U m 250 V (Attention! The rated voltage is lower.), RS 232Maximum safe voltage | U m | 250 V (Attention! The rated voltage is lower.), RS 232
Maximum safe voltage U m 250 V (Attention! This is not the rated voltage.)Maximum safe voltage | U m | 250 V (Attention! This is not the rated voltage.)
Measuring currentapprox. 200 µA with RTD
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided.
Power consumptionmax. 0.98 W
Power dissipation≤ 0.98 W
Power P o30 mW
Rated voltageU r | 19 ... 30 V DC
Voltageselectable within the range -100 ... 100 mV
Voltage U o9 V
Voltage U o 9 V Current I o 13.1 mA Power P o 30 mWVoltage U o | 9 V | Current I o | 13.1 mA | Power P o | 30 mW
AC and DC characteristics
Protection against electrical shockUL 61010-1:2004
Ripplewithin the supply tolerance
Environment and package
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Influence of ambient temperaturePt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔT amb *) thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔT amb *) ), influence of cold junction compensation (CJC) included mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔT amb *) potentiometer: ± 0.006 % of span/K ΔT amb *) *) ΔT amb = ambient temperature change referenced to 23 °C (296 K)
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Other
After calibrationPt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection)) thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1.5 K (1.7 K for types R and S)) , includes ± 1.3 K fault of the cold junction compensation (CJC) mV: ± (50 µV + 0.1 % of span) potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes faults due to lead resistance))
CertificateBASEEFA 13 ATEX 0103 X
Cold junction compensationexternal and internal
Cold junction compensation external and internal Measurement loop monitoring sensor breakageCold junction compensation | external and internal | Measurement loop monitoring | sensor breakage
Configurationvia PACTware
Connectionterminals 9+, 10- or power feed module/Power Rail
Connection sidefield side
Control drawing116-0379 (cULus)
Control drawing 116-0379 (cULus)Control drawing | 116-0379 (cULus)
Degree of protectionIEC 60529:2001
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN 60079-15:2010
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN 60079-15:2010Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN 60079-15:2010
Display elementsLEDs
Electromagnetic compatibilityNE 21:2012 EN 61326-3-2:2008
EU-type examination certificateBASEEFA 13 ATEX 0102 X
Fault signaldownscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
IECEx certificateIECEx BAS 13.0057X
IECEx certificate IECEx BAS 13.0057X IECEx marking [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] IIECEx certificate | IECEx BAS 13.0057X | IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Influence of load≤ 0.001 % of output value per 100 Ω
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input resistance≥ 1 MΩ (-100 ... 100 mV)
Inputsterminals 1, 2, 3, 4
Labelingspace for labeling at the front
Lead resistancemax. 50 Ω per line
MarkingII (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I
Marking II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I Input [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] IMarking | II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC , [exsign] I (M1) [Ex ia Ma] I | Input | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Marking II 3G Ex nA IIC T4 GcMarking | II 3G Ex nA IIC T4 Gc
Massapprox. 100 g
Measurement loop monitoringsensor breakage, sensor short-circuit
OutputAnalog current output
Potentiometer0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Programming interfaceprogramming socket
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760)
Safety Integrity Level (SIL)SIL 2
Signal typeAnalog input
SinkVoltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V, series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 5)/0.0215 Ω.
Sourceload 0 ... 550 Ω open-circuit voltage ≤ 18 V
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) type TXK, TXKH, TXA (P8.585-2001)
Types of measuring2-, 3-, 4-wire connection

Documents

No documents are linked to this part yet.