All alternatives

View full report

Technical parameters

Power
Available voltage≥ 15 V at 20 mA , ≥ 18 V at 4 mA on SL2: 5a(+), 5b(-)
CurrentI o | 100 mA
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Maximum safe voltageU m | 250 V AC (Attention! U m is no rated voltage.)
Maximum safe voltage U m 250 V AC (Attention! U m is no rated voltage.)Maximum safe voltage | U m | 250 V AC (Attention! U m is no rated voltage.)
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 60 V eff
PowerP o | 630 mW
Power consumption≤ 1.1 W
Power dissipation≤ 800 mW
Rated currentI r | ≤ 45 mA at 24 V and 20 mA source mode output
Rated voltageU r | 19 ... 30 V DC bus powered via Termination Board
VoltageU o | 25.2 V
Voltage dropapprox. 5 V on SL2: 5a(+), 1b(-)
Voltage U o 25.2 V Current I o 100 mA Power P o 630 mW Internal capacitance C i 5.7 nF Internal inductance L i negligibleVoltage | U o | 25.2 V | Current | I o | 100 mA | Power | P o | 630 mW | Internal capacitance | C i | 5.7 nF | Internal inductance | L i | negligible
AC and DC characteristics
Frequency rangefield side into the control side: bandwidth with 0.5 V pp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 V pp signal 0 ... 3 kHz (-3 dB)
Protection against electrical shockUL 61010-1:2018
Ripple≤ 10 %
Rise time/fall time≤ 10 ms
Settling time≤ 50 ms
Environment and package
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode and sink mode 4 ... 20mA) < 0.5 mV/K (-20 ... 70 °C (-4 ... 158 °F)); < 1 mV/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode 1...5 V)
Mountingon termination board
Other
CertificateCESI 19 ATEX 027 X
Codingpin 1 and 3 trimmed For further information see system description.
Configurationvia DIP switches
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Connection sidefield side
Control drawing116-0470 (cFMus)
Control drawing 116-0458 (cULus)Control drawing | 116-0458 (cULus)
Control elementsDIP switch
Degree of protectionIEC 60529:2001
Deviationat 20 °C (68 °F) < 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4 ... 20 mA) ≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN IEC 60079-7:2015/A1:2018
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN IEC 60079-7:2015/A1:2018Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN IEC 60079-11:2024 , EN IEC 60079-7:2015/A1:2018
Display elementsLED
Electromagnetic compatibilityNE 21:2017 EN 61326-3-2:2018 For further information see system description.
EquipmentSL2: 5a(+), 5b(-)
EU-type examination certificateCESI 06 ATEX 017
Factory settingoutput: current source
FM certificateFM 19 US 0122 X , FM 19 CA 0065 X
FM certificate FM 19 US 0122 X , FM 19 CA 0065 X Control drawing 116-0470 (cFMus)FM certificate | FM 19 US 0122 X , FM 19 CA 0065 X | Control drawing | 116-0470 (cFMus)
IECEx certificateIECEx CES 06.0002X
IECEx certificate IECEx CES 06.0002X IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 GcIECEx certificate | IECEx CES 06.0002X | IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc
InputEx ia
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input signal4 ... 20 mA limited to approx. 26 mA
Internal capacitanceC i | 5.7 nF
Internal inductanceL i | negligible
Labelingspace for labeling at the front
Load0 ... 350 Ω (source mode)
MarkingII (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Marking II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I Input Ex iaMarking | II (1)G [Ex ia Ga] IIC [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I | Input | Ex ia
Marking II 3G Ex ec IIC T4 GcMarking | II 3G Ex ec IIC T4 Gc
Massapprox. 100 g
Output signalsource mode: 4 ... 20 mA or 1 ... 5 V (internal resistor: 250 Ω, 0.1 %) sink mode: 4 ... 20 mA, operating voltage 10 ... 30 V For additional internal or external loads the voltage drop has to be considered, e. g. 250 Ω x 20 mA = 5 V.
Safety Integrity Level (SIL)SIL 2
Signal typeAnalog input
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Systematic capability (SC)SC 3
UL approvalE106378

Documents

No documents are linked to this part yet.