All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Current | I e | typ. 45 mA |
| Current limit | I max | 50 mA |
| Input current | 75 mA at 24 V, 270 Ω load |
| Input/Output safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rms | Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rms |
| Inrush current | < 200 mA , 10 ms loop powered |
| Maximum safe voltage | U m | 60 V (Attention! The rated voltage can be lower.) |
| Maximum safe voltage U m 60 V (Attention! The rated voltage can be lower.) | Maximum safe voltage | U m | 60 V (Attention! The rated voltage can be lower.) |
| Open loop voltage | U s | typ. 24.6 V |
| Power | P o | 715 mW |
| Power dissipation | 1.3 W at 24 V, 270 Ω load |
| Rated current | I r | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
| Rated voltage | U r | 19 ... 30 V bus powered via Termination Board 19 ... 30 V loop powered via input , reverse polarity protected |
| Test current | max. 350 µA , calculated by I LFD = 4.7 V / (15 kΩ + R Load ) |
| Test current max. 350 µA , calculated by I LFD = 4.7 V / (15 kΩ + R Load ) | Test current | max. 350 µA , calculated by I LFD = 4.7 V / (15 kΩ + R Load ) |
| Voltage | U e | ≥ 12 V |
| AC and DC characteristics | |
| Energized/De-energized delay | 20 ms / 5 ms |
| Protection against electrical shock | UL 61010-1:2012 |
| Switching frequency | f | max. 10 Hz |
| Environment and package | |
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Dimensions | 12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D) |
| Mounting | on termination board |
| Other | |
| Coding | pin 1 and 4 trimmed For further information see system description. |
| Configuration | via DIP switches |
| Connection | SL1: 1a, 1b(-); 2a, 2b(+) |
| Connection side | control side |
| Control drawing | 116-0442 |
| Control drawing 116-0442 | Control drawing | 116-0442 |
| Control drawing 116-0447A (cULus) | Control drawing | 116-0447A (cULus) |
| Control elements | DIP switch |
| Degree of protection | IEC 60529:2013 |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/30/EU EN 61326-1:2013 (industrial locations) | Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 |
| Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 | Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 |
| Display elements | LEDs |
| Electromagnetic compatibility | NE 21:2017 , IEC/EN 61326-3-2:2018 For further information see system description. |
| EU-type examination certificate | FIDI 21 ATEX 0069X |
| FM approval | FM 17 US 0111 X , FM 17 CA 0057 X |
| IECEx certificate | IECEx EXA 17.0009X |
| IECEx certificate IECEx EXA 17.0009X IECEx marking Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I | IECEx certificate | IECEx EXA 17.0009X | IECEx marking | Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
| IECEx marking | Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rms |
| Internal resistor | R i | approx. 240 Ω |
| Labeling | space for labeling at the front |
| Load | nominal 0.05 ... 18 kΩ , valid range for line fault detection (LFD) |
| Marking | II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I |
| Mass | approx. 150 g |
| Output | Ex ia |
| Output/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff |
| Output type | open collector transistor (internal fault bus) |
| Safety Integrity Level (SIL) | SIL 3 |
| Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC |
| Signal type | Digital Output |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| Systematic capability (SC) | SC 3 |
| Test pulse length | max. 2 ms from DO card |
| UL approval | E106378 |
Documents
No documents are linked to this part yet.