All alternatives

View full report

Technical parameters

Power
CurrentI e | typ. 45 mA
Current limitI max | 50 mA
Input current75 mA at 24 V, 270 Ω load
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rmsInput/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rms
Inrush current< 200 mA , 10 ms loop powered
Maximum safe voltageU m | 60 V (Attention! The rated voltage can be lower.)
Maximum safe voltage U m 60 V (Attention! The rated voltage can be lower.)Maximum safe voltage | U m | 60 V (Attention! The rated voltage can be lower.)
Open loop voltageU s | typ. 24.6 V
PowerP o | 715 mW
Power dissipation1.3 W at 24 V, 270 Ω load
Rated currentI r | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card)
Rated voltageU r | 19 ... 30 V bus powered via Termination Board 19 ... 30 V loop powered via input , reverse polarity protected
Test currentmax. 350 µA , calculated by I LFD = 4.7 V / (15 kΩ + R Load )
Test current max. 350 µA , calculated by I LFD = 4.7 V / (15 kΩ + R Load )Test current | max. 350 µA , calculated by I LFD = 4.7 V / (15 kΩ + R Load )
VoltageU e | ≥ 12 V
AC and DC characteristics
Energized/De-energized delay20 ms / 5 ms
Protection against electrical shockUL 61010-1:2012
Switching frequencyf | max. 10 Hz
Environment and package
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Mountingon termination board
Other
Codingpin 1 and 4 trimmed For further information see system description.
Configurationvia DIP switches
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Connection sidecontrol side
Control drawing116-0442
Control drawing 116-0442Control drawing | 116-0442
Control drawing 116-0447A (cULus)Control drawing | 116-0447A (cULus)
Control elementsDIP switch
Degree of protectionIEC 60529:2013
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)Directive 2014/30/EU | EN 61326-1:2013 (industrial locations)
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
Display elementsLEDs
Electromagnetic compatibilityNE 21:2017 , IEC/EN 61326-3-2:2018 For further information see system description.
EU-type examination certificateFIDI 21 ATEX 0069X
FM approvalFM 17 US 0111 X , FM 17 CA 0057 X
IECEx certificateIECEx EXA 17.0009X
IECEx certificate IECEx EXA 17.0009X IECEx marking Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] IIECEx certificate | IECEx EXA 17.0009X | IECEx marking | Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
IECEx markingEx nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 V rms
Internal resistorR i | approx. 240 Ω
Labelingspace for labeling at the front
Loadnominal 0.05 ... 18 kΩ , valid range for line fault detection (LFD)
MarkingII 3(1)G Ex nC ec [ia Ga] IIC T4 Gc [exsign] II (1)D [Ex ia Da] IIIC [exsign] I (M1) [Ex ia Ma] I
Massapprox. 150 g
OutputEx ia
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 V eff
Output typeopen collector transistor (internal fault bus)
Safety Integrity Level (SIL)SIL 3
Signal levelloop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC
Signal typeDigital Output
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Systematic capability (SC)SC 3
Test pulse lengthmax. 2 ms from DO card
UL approvalE106378

Documents

No documents are linked to this part yet.