All alternatives
View full reportTechnical parameters
| Power | |
|---|---|
| Nominal voltage | U o | 8.2 V (R i approx. 1 kΩ) |
| AC and DC characteristics | |
| Switching frequency | f | 0 ... 200 Hz |
| Environment and package | |
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Other | |
| Actual operating distance | s r | 9 ... 11 mm typ. |
| ANZEx | 18.3018X |
| Assured operating distance | s a | 0 ... 8.1 mm |
| Bending radius | > 10 x cable diameter |
| Cable diameter | 6 mm ± 0.2 mm |
| CML approval | on request |
| Color | blue |
| Connection type | cable |
| Control drawing | 116-0452 |
| Core cross section | 0.75 mm 2 |
| Degree of protection | IP66 / IP67 |
| Diagnostic Coverage (DC) | 0 % |
| Diameter | 30 mm |
| Equipment protection level Da | IECEx PTB 11.0037X |
| Equipment protection level Dc (tc) | IECEx TUR 21.0018X |
| Equipment protection level Ga | IECEx PTB 11.0037X |
| Equipment protection level Gb | IECEx PTB 11.0037X |
| Equipment protection level Mb | IECEx PTB 11.0037X |
| Hazardous Location | E501628 |
| Hazardous Location 09-AV4BO-0226 | Hazardous Location | 09-AV4BO-0226 |
| Hazardous Location 2020322315002255 2024322315005860 | Hazardous Location | 2020322315002255 2024322315005860 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Hysteresis | H | 1 ... 15 % typ. 5 % |
| Installation | flush |
| Length | L | 10 m |
| Length 40 mm Diameter 30 mm | Length | 40 mm | Diameter | 30 mm |
| Mass | 632 g |
| Material | PVC |
| Measuring plate detected | ≤ 1 mA |
| Measuring plate not detected | min. 2.2 mA |
| Measuring plate not detected min. 2.2 mA Measuring plate detected ≤ 1 mA | Measuring plate not detected | min. 2.2 mA | Measuring plate detected | ≤ 1 mA |
| Mission Time (T M ) | 20 a |
| MTTF d | 1870 a |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Standards EN IEC 60947-5-2 | NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Standards | EN IEC 60947-5-2 |
| Number of cores | 2 |
| Ordinary Location | E87056 |
| Ordinary Location E87056 Hazardous Location E501628 Control drawing 116-0452 | Ordinary Location | E87056 | Hazardous Location | E501628 | Control drawing | 116-0452 |
| Output type | NAMUR |
| Rated operating distance | s n | 10 mm |
| Reduction factor r 304 | 0.75 |
| Reduction factor r Al | 0.35 |
| Reduction factor r Cu | 0.3 |
| Reverse polarity protection | reverse polarity protected |
| Scope of delivery | 2 self locking nuts in scope of delivery |
| Sensing face | PBT |
| Short-circuit protection | yes |
| Standards | EN IEC 60947-5-2 |
| Switching function | Normally closed (NC) |
| Switching state indicator | all direction LED, yellow |
| UL approval | cULus Listed Load Type: General Purpose Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC |
| Use in the hazardous area | see instruction manuals |
| Wire end ferrules | yes |
Documents
No documents are linked to this part yet.