All alternatives

View full report

Technical parameters

Power
Nominal voltageU o | 8.2 V (R i approx. 1 kΩ)
AC and DC characteristics
Switching frequencyf | 0 ... 100 Hz
Environment and package
Ambient temperature-40 ... 100 °C (-40 ... 212 °F)
Height40 mm
Height 40 mm Width 80 mm Length 80 mmHeight | 40 mm | Width | 80 mm | Length | 80 mm
Other
Assured operating distances a | 0 ... 32.4 mm
Connection type1/2 NPT terminal compartment, wire cross-section ≤ 2.5 mm 2
Core cross sectionup to 2.5 mm 2
Degree of protectionIP68
Diagnostic Coverage (DC)0 %
Equipment protection level DaIECEx PTB 11.0092X
Equipment protection level GbIECEx PTB 11.0092X
Equipment protection level Gb IECEx PTB 11.0092X Equipment protection level Da IECEx PTB 11.0092XEquipment protection level Gb | IECEx PTB 11.0092X | Equipment protection level Da | IECEx PTB 11.0092X
Equipment protection level Gb PTB 00 ATEX 2049 X Equipment protection level Da PTB 00 ATEX 2049 XEquipment protection level Gb | PTB 00 ATEX 2049 X | Equipment protection level Da | PTB 00 ATEX 2049 X
Hazardous Location18-AV4BO-0478X
Hazardous Location 18-AV4BO-0478XHazardous Location | 18-AV4BO-0478X
Housing materialPBT/metal
Installationnon-flush
Length80 mm
Measuring plate detected≤ 1 mA
Measuring plate not detectedmin. 3 mA
Measuring plate not detected min. 3 mA Measuring plate detected ≤ 1 mAMeasuring plate not detected | min. 3 mA | Measuring plate detected | ≤ 1 mA
Mission Time (T M )20 a
MTTF d7560 a
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
NAMUR EN 60947-5-6:2000 IEC 60947-5-6:1999 Standards EN IEC 60947-5-2NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | Standards | EN IEC 60947-5-2
Output typeNAMUR with safety function
Rated operating distances n | 40 mm
Reduction factor r 3040.85
Reduction factor r Al0.4
Reduction factor r Cu0.3
Sensing facePBT
StandardsEN IEC 60947-5-2
Switching functionNormally closed (NC)
UL approvalcULus Listed Load Type: General Purpose Circuitry: Class 2 Power Source Enclosure Type Rating: Type 1 Supply/Switching Voltage: 8.2 V DC
Use in the hazardous areasee instruction manuals
Width80 mm

Documents

No documents are linked to this part yet.