| 电源 | |
|---|---|
| Current | I o | 108 mA |
| Current limit | I max | 40 mA both channels parallel 80 mA |
| Number of channels | 2 |
| Open loop voltage | U s | 23 V , both channels parallel 23 V |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Output/power supply, internal bus safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V |
| Power | P o | 654 mW |
| Power consumption | 2.9 W |
| Power dissipation | 1.95 W |
| Rated voltage | U r | Use only in connection with the power supplies LB9*** |
| Voltage | U o | 24.2 V |
| Voltage U o 24.2 V Current I o 108 mA Power P o 654 mW Internal capacitance C i 12 nF Internal inductance L i 0 mH | Voltage | U o | 24.2 V | Current | I o | 108 mA | Power | P o | 654 mW | Internal capacitance | C i | 12 nF | Internal inductance | L i | 0 mH |
| Voltage U o 24.2 V Current I o 216 mA Power P o 1307 mW Internal capacitance C i 24 nF Internal inductance L i 0 mH | Voltage | U o | 24.2 V | Current | I o | 216 mA | Power | P o | 1307 mW | Internal capacitance | C i | 24 nF | Internal inductance | L i | 0 mH |
| 环境与封装 | |
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) |
| Height | 100 mm |
| Height 100 mm Width 16 mm Depth 102 mm | Height | 100 mm | Width | 16 mm | Depth | 102 mm |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| 其他 | |
| Altitude | max. 2000 m |
| Approved for | Ex nA [ic] IIC T4 Gc |
| Approved for Ex nA [ic] IIC T4 Gc | Approved for | Ex nA [ic] IIC T4 Gc |
| ATEX approval | EXA 16 ATEX 0035X |
| Coding | optional mechanical coding via front socket |
| Connection | backplane bus |
| Damaging gas | EN 60068-2-42 |
| Degree of protection | IEC 60529 |
| Depth | 102 mm |
| Directive 2014/30/EU | EN 61326-1:2013 |
| Directive 2014/30/EU EN 61326-1:2013 | Directive 2014/30/EU | EN 61326-1:2013 |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 |
| Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 | Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 EN 60079-11:2012 EN 60079-15:2010 |
| Electromagnetic compatibility | NE 21 |
| Environmental test | EN 60068-2-14 |
| EU-type examination certificate | EXA 16 ATEX 0035X |
| Field device | Solenoid Valve |
| Field device [2] | audible alarm |
| Field device [3] | visual alarm |
| Field device Solenoid Valve Field device [2] audible alarm Field device [3] visual alarm | Field device | Solenoid Valve | Field device [2] | audible alarm | Field device [3] | visual alarm |
| IECEx approval | IECEx EXA 16.0010X |
| Interface | manufacturer-specific bus to standard com unit |
| Internal capacitance | C i | 12 nF |
| Internal inductance | L i | 0 mH |
| Internal resistor | R i | 258 Ω , both channels parallel 129 Ω |
| LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs |
| Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc |
| Marking II 3 G Ex nA [ic] IIC T4 Gc | Marking | II 3 G Ex nA [ic] IIC T4 Gc |
| Mass | approx. 150 g |
| Occupied slots | 1 |
| Open-circuit | > 10 kΩ |
| Relative humidity | EN 60068-2-78 |
| Response time | 10 ms (depending on bus cycle time) |
| Shock resistance | EN 60068-2-27 |
| Short-circuit | < 50 Ω |
| Short-circuit < 50 Ω Open-circuit > 10 kΩ | Short-circuit | < 50 Ω | Open-circuit | > 10 kΩ |
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
| System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2, Zone 22 or Div. 2) the module must be installed in an appropriate enclosure. |
| Vibration resistance | EN 60068-2-6 |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication |
| Width | 16 mm |